0 引言
RCS-9681C模塊主要(yao)(yao)用(yong)于110kV電(dian)(dian)(dian)壓(ya)等(deng)級(ji)或以下等(deng)級(ji)變壓(ya)器的(de)(de)110kV,或35kV或10kV側后(hou)備保(bao)(bao)護(hu)(hu)裝(zhuang)置(zhi),主要(yao)(yao)包括復壓(ya)過(guo)(guo)流(liu)保(bao)(bao)護(hu)(hu)、零序過(guo)(guo)流(liu)保(bao)(bao)護(hu)(hu)。文主要(yao)(yao)分析復壓(ya)過(guo)(guo)流(liu)保(bao)(bao)護(hu)(hu)。復壓(ya)過(guo)(guo)流(liu)保(bao)(bao)護(hu)(hu)是由一(yi)(yi)個(ge)負序電(dian)(dian)(dian)壓(ya)繼電(dian)(dian)(dian)器和一(yi)(yi)個(ge)接在相間電(dian)(dian)(dian)壓(ya)上的(de)(de)低電(dian)(dian)(dian)壓(ya)繼電(dian)(dian)(dian)器組成的(de)(de)復合電(dian)(dian)(dian)壓(ya)元(yuan)件(jian),這兩個(ge)電(dian)(dian)(dian)壓(ya)元(yuan)件(jian)是“或”的(de)(de)關系(xi),同時過(guo)(guo)流(liu)繼電(dian)(dian)(dian)器動作,啟動復壓(ya)過(guo)(guo)流(liu)保(bao)(bao)護(hu)(hu)。
1 校驗(yan)前(qian)準備(bei)
接線(xian)說明:微(wei)機(ji)(ji)型繼電(dian)(dian)保(bao)(bao)護測(ce)試(shi)儀三相電(dian)(dian)壓輸出(chu)(chu)(四根線(xian))“UA、UB、UC、UN”接入保(bao)(bao)護屏“31D”端(duan)子(zi)排(pai)的(de)12、13、14、15(注意(yi)合(he)上(shang)31ZKK 后(hou),保(bao)(bao)護裝置才會(hui)有(you)交流電(dian)(dian)壓)。微(wei)機(ji)(ji)型繼電(dian)(dian)保(bao)(bao)護測(ce)試(shi)儀三相電(dian)(dian)流輸出(chu)(chu)(四根線(xian))“IA、IB、IC、IN ”接入保(bao)(bao)護屏“31D”端(duan)子(zi)排(pai)的(de)1、2、3、4 號端(duan)子(zi)。繼電(dian)(dian)保(bao)(bao)護測(ce)試(shi)儀開關量 A(任意(yi)一組即可)與保(bao)(bao)護屏“PD”端(duan)子(zi)排(pai)的(de)3,“ND”端(duan)子(zi)排(pai)的(de)3號端(duan)子(zi)相接。如圖1所(suo)示。
RCS-9681CS交流回路校驗。在進行該相測試前,應退開所有壓板,保證保護不動作,觀察采樣值。通過繼電保護測試儀分別加入額定電UA=UB=UC=57.7V,電流IA=IB=IC=5A,進入保護裝置的“保護狀態”菜單中“DSP采樣值”子菜單中讀取采樣值,采樣值應與實際加入值相等,其誤差應小于±5%。測試結果如表1所示。
2 復壓過流保護(hu)校驗
RCS-9681裝置設置。打開RCS-9681裝置,按“上”鍵→進入“菜單選擇”→進入“裝置整定”,改變定值如下:(1)“保護定值”中記錄:復壓過流I段電流定值設為6A;復壓過流Ⅰ段時間為0s;負序電壓為6V;低電壓定值為60V。“復壓過流I段投入”控制字置“1”,其他II、III、IV、V、VI段控制字置“0”;“過流I段經復合電壓閉鎖”置“1”,其他 II、III、IV、V、VI段控制字置“0”。(2)“軟壓板修改”中“過流I 段軟壓板”置“1”。(3)硬壓板:投復壓過流,跳高壓側。
繼電保護測試(shi)儀設(she)置。選(xuan)擇“交流(liu)實驗(yan)”菜(cai)單(dan):(1)電流(liu)動作(zuo)值(zhi)校(xiao)驗(yan)。UA=UB=UC=30V,IA=IB=IC=0A且(qie)三相電流(liu)同(tong)時可變(bian)(bian),相位(wei)為0°、240°、120°,電流(liu)變(bian)(bian)化步長0.1A,每步時長1s,選(xuan)擇“自(zi)動試(shi)驗(yan)”“動作(zuo)停(ting)止”,點擊“開始(shi)試(shi)驗(yan)”。裝置報(bao)文(wen):ABC Imax5.99A,復壓過流(liu)I段(duan)動作(zuo)。測試(shi)結果(guo):電流(liu)動作(zuo)值(zhi)5.99A。
電(dian)流(liu)(liu)返回值校驗(yan)。UA=UB=UC=30V,IA=IB=IC=6.00A且三相(xiang)電(dian)流(liu)(liu)幅(fu)值同時可變,三相(xiang)電(dian)壓、電(dian)流(liu)(liu)相(xiang)位均為0°、240°、120°,電(dian)流(liu)(liu)變化步長0.1A,每步時長1s,選擇“自動試(shi)驗(yan)”“動作(zuo)返回”,點擊“開始試(shi)驗(yan)”。裝(zhuang)置報文(wen): A B CImax6.02A 復壓過流(liu)(liu)I段動作(zuo)。測試(shi)結果:返回電(dian)流(liu)(liu)值5.8A。
低電壓動作值校驗。UA=UB=UC=40V且三相電壓幅值同時可變,IA=IB=IC=6.0A,三相電壓、電流相位均為0°、240°、120°,電壓變化步長-0.5V,每步時長1s,選擇“自動試驗”“動作停止”,點擊“開始試驗”。裝置報文: A B CImax5.98A 復壓過流I段動作。低電壓動作動作值: UA=UB=UC=34.95VUAB=UBC=UCA=60.77V,誤(wu)差1.3%。
負序電(dian)壓(ya)(ya)動(dong)作(zuo)值(zhi)(zhi)校(xiao)驗。將低電(dian)壓(ya)(ya)定(ding)值(zhi)(zhi)為70V改為2V,不讓相間低電(dian)壓(ya)(ya)開放復壓(ya)(ya)。UA=UB=UC=4V且(qie)電(dian)壓(ya)(ya)幅值(zhi)(zhi)同時可變(bian);IA=IB=IC=6A,三(san)相電(dian)壓(ya)(ya)、電(dian)流相位均(jun)為0°、120°、240,電(dian)壓(ya)(ya)變(bian)化步長0.5V,每(mei)步時長1s,選擇“自(zi)動(dong)試(shi)驗”“動(dong)作(zuo)停止”,點擊“開始試(shi)驗”。參數設置(zhi)(zhi)(zhi)如(ru)圖(tu)5所示。裝(zhuang)置(zhi)(zhi)(zhi)報文:ABCImax6.00A 復壓(ya)(ya)過(guo)流I段(duan)(duan)(duan)動(dong)作(zuo)。測試(shi)結果:負序電(dian)壓(ya)(ya)動(dong)作(zuo)值(zhi)(zhi)U2=5.98V,誤差0.3%。復壓(ya)(ya)過(guo)流動(dong)作(zuo)邊(bian)界(jie)校(xiao)驗。(1)保(bao)(bao)護柜設置(zhi)(zhi)(zhi)。打開RCS-9681裝(zhuang)置(zhi)(zhi)(zhi),按“上”鍵(jian)→菜單選擇→裝(zhuang)置(zhi)(zhi)(zhi)整定(ding),改變(bian)定(ding)值(zhi)(zhi)如(ru)下(xia):①“保(bao)(bao)護定(ding)值(zhi)(zhi)”中(zhong)“復壓(ya)(ya)過(guo)流I段(duan)(duan)(duan)投入”控(kong)制(zhi)字置(zhi)(zhi)(zhi)“1”,其(qi)(qi)他(ta) II、III、IV、V、VI 段(duan)(duan)(duan)控(kong)制(zhi)字置(zhi)(zhi)(zhi)“0”;“過(guo)流 I 段(duan)(duan)(duan)復壓(ya)(ya)閉鎖”置(zhi)(zhi)(zhi)“1”,其(qi)(qi)他(ta) II、III、IV、V、VI 段(duan)(duan)(duan)控(kong)制(zhi)字置(zhi)(zhi)(zhi)“0”;“過(guo)流I段(duan)(duan)(duan)方向(xiang)(xiang)閉鎖”控(kong)制(zhi)字置(zhi)(zhi)(zhi)“1”,其(qi)(qi)他(ta) II、III、IV、V、VI 段(duan)(duan)(duan)控(kong)制(zhi)字置(zhi)(zhi)(zhi)“0”;“過(guo)流保(bao)(bao)護方向(xiang)(xiang)指(zhi)向(xiang)(xiang)”置(zhi)(zhi)(zhi)“1”,“其(qi)(qi)他(ta)側(ce)
復壓閉鎖”置“1”。②“軟壓板修改”中“過流I段軟壓板”置“1”。③硬壓板:投復壓過流,跳低壓側,跳高壓側。(2)繼電保護測試儀設置。UA=30V,UB=UC=0V,其中UA相位為225°;IA=6A,相位0°,IB=IC=0A。保護應動作。減小A相電壓相位,直至保護不動作,找到動作區的一個動作邊界。增大A相電壓相位,角度向另外一個方向變化,直至保護不動作,得到動作區的另外一個邊界。裝置報文:A Imax6.01A 復壓過流I段動作。測試結果:動作邊界180°,-270°。
3 結(jie)語(yu)
變(bian)壓器(qi)是(shi)變(bian)電站主(zhu)要設備之(zhi)一,因此當它發生故障而(er)主(zhu)保(bao)護(hu)未能及(ji)時可靠動作時,后(hou)(hou)備保(bao)護(hu)的(de)可靠及(ji)時動作對電力系統安(an)全穩定運行尤為重要,而(er)復合電壓閉鎖過電流保(bao)護(hu)校(xiao)驗(yan)是(shi)變(bian)壓器(qi)的(de)主(zhu)要后(hou)(hou)備保(bao)護(hu)校(xiao)驗(yan)的(de)重要部分,因此后(hou)(hou)備保(bao)護(hu)的(de)定期校(xiao)驗(yan)保(bao)證其工作正(zheng)常(chang)。